● Non-contact detector clips. No metal contact points to
advocate greater safety.
● Two functions in one unit : open phase and phase
sequence detection.
● Designed for checking a wider range of 3-phase power
sources.
● LED display lights with buzzer indicator.
● Brightness button feature for better visibility in dimly lit
areas or sunlight.
● Magnetic mounting feature.
Measurement principle | Static induction | |
Input voltage | 75~1000Vac | |
Frequency range | 45-65Hz | |
Auto-off | 5 min. after power on without detection | |
Low battery warning | Power LED flashes at 7V ± 0.2 or less | |
Operating temperature & humidity | 0°C ~ 40°C Max. 80% R.H. | |
Storage temperature & humidity | -10°C ~ 50°C Max. 80% R.H. | |
Cable length | Approx. 800mm | |
Dimensions | 128(L) × 72(W) × 44(D)mm | |
Weight (battery included) | Approx. 380g | |
Power source | 9V (6LF22) × 1 | |
Safety standard | EN 61010-1 CAT III 1000V / CAT IV 600V EN 61326-1 EN 61557-1 EN 61557-7 |