MRU-200 is the only meter in the market which uses all measurement methods.
Possible measurements:
- earth resistance measurment with 2-pole, 3-pole,4-pole method,
- impulse earth impedance measurement, two kinds of measuring impulse 4/10μs, 10/350μs,
- earth resistance measurement without disconnecting measured earths (using clamp),
- two clamps earth resistance measurement without auxiliary test probs,
- earth resistivity measurement,
- continuity measurement,
- leakage current measurement.
Possible measurements:
- earth resistance measurment with 2-pole, 3-pole,4-pole method,
- impulse earth impedance measurement, two kinds of measuring impulse 4/10μs, 10/350μs,
- earth resistance measurement without disconnecting measured earths (using clamp),
- two clamps earth resistance measurement without auxiliary test probs,
- earth resistivity measurement,
- continuity measurement,
- leakage current measurement.
It allows to take the measurements of:
- earth resistance using auxiliary electrodes,
- earth resistance using auxiliary electrodes and clamp (for measurements of multiple earthing)
- earth resistance using double clamps (for measurement of earthing when it is impossible to use auxiliary electrodes),
- impulse earth impedance (without disconnecting measured earthing),
- ground resistivity (Wenner method),
- current using the clamp (e.g. leakage) and flexible clamp (Rogowsky coil),
- measurement of continuity of equipotential bondings and protective conductors (meeting the requirements of IEC 60364-6-61:2000 section 6.12.2) with auto-zero function – with current 200mA.
Additionally:
- measurement of resistance of auxiliary electrodes RS and RH,
- measurement of interference voltage,
- measurement of interference frequency,
- measurement in the presence of interference voltage in the power network
with frequency 16 2/3 Hz, 50Hz, 60Hz and 400Hz (with automatic selection of proper frequency of measuring signal or with manual selection), - selection of maximum measuring voltage (25V and 50V)
- introducing the distance between the electrodes for the resistivity in metres (m) and feet (ft),
- memory of 990 measurements (10 banks of 99 cells each),
- calibration of clamp used,
- real time clock (RTC),
- data transmission to the computer (USB),
- indication of battery state.
- type of insulation: double, according to EN 61010-1 and IEC 61557
- measurement category: CAT IV 300V acc. to EN 61010-1
- protection class acc. to EN 60529: IP54
Rated operational conditions:
- operation temperature: -10...+50°C
- storage temperature: -20...+70°C
- humidity: 20...80%
Other technical data:
- LCD display: graphic, backlighted
- interface: USB
- number of measurements carried out of set of batteries: > 1200
- warranty: 36 months
Measurement of interference voltage
Range | Resolution | Accuracy |
0...100V | 1V | ±(2% m.v. + 3 digits) |
Measurement of interference frequency
Range | Resolution | Accuracy |
15...450Hz | 1Hz | ±(1% m.v. + 2 digits) |
Measurement of earthing resistance (method 3- and 4-pole)
measurement range to IEC61557-5: 0,100Ω...19,9kΩ
Range | Resolution | Accuracy |
0,000...3,999Ω | 0,001Ω | ±(2% m.v. + 4 digits) |
4,00...39,99Ω | 0,01Ω | ±(2% m.v. + 2 digits) |
40,0...399,9Ω | 0,1Ω | |
400...3999Ω | 0,001kΩ | |
4,00k...19,99kΩ | 0,01kΩ | ±(5% m.v. + 2 digits) |
Measurement of continuity of equipotential bondings and protective conductors (Rcont)
measurement range to IEC61557-4: 0,045Ω...19,99kΩ
Range | Resolution | Accuracy |
0,000...3,999Ω | 0,001Ω | ±(2% m.v. + 4 digits) |
4,00...39,99Ω | 0,01Ω | ±(2% m.v. + 2 digits) |
40,0...399,9Ω |
0,1Ω |
|
400...3999Ω | 0,001kΩ | |
4,00k...19,99kΩ | 0,01kΩ | ±(5% m.v. + 2 digits) |
Measurement of resistance of auxiliary electrodes RH and RS
Range | Range | Accuracy |
0...999Ω | 1Ω | ±(5% (RS+RE+RH) + 8 digits) |
1,00k...9,99kΩ | 0,01kΩ | |
10,0k...19,9kΩ | 0,1kΩ |
Measurement of multiple earthing resistance with using the clamp and auxiliary
electrodes (3p + clamp) measurement range to IEC61557-5: 0,120Ω...1,99kΩ
Range | Resolution | Accuracy |
0,000...3,999Ω* | 0,01Ω | ±(8% m.v. + 4 digits) |
10,0...99,9Ω | 0,01Ω | ±(8% m.v. + 3 digits) |
100...999Ω | 0,1Ω | |
1,00k...1,99kΩ | 1Ω |
Measurement of multiple earthing resistance with using double clamps
Range | Resolution | Accuracy |
0,00...19,99Ω | 0,1Ω | ±(10% m.v. + 3 digits) |
20,0...149,9Ω | 0,1Ω | ±(20% m.v. + 3 digits) |
Measurement of ground resistivity Measurement method: Wennera, ρ=2πLRE
Range | Resolution | Accuracy |
0,0...199,9Ωm | 0,1Ωm | depending on measurement accuracy RE with 4p method, but not less than ±1 digit |
200...1999Ωm | 1Ωm | |
2,00k...19,99kΩm | 0,01kΩm | |
20,0k...99,9kΩm | 0,1kΩm | |
100k...999kΩm | 1kΩm |
Measurement of AC current (leakage)
Range | Resolution | Accuracy |
0,1...99,9mA 1 | 0,1mA | ±(8% m.v. + 5 digits) |
100...999mA 1 | 1mA | ±(8% m.v. + 3 digits) |
1,00...4,99A 1,2 | 0,01A | ±(5% m.v. + 5 digits)1 unspecified 2 |
5,00...9,99A 1,2 | 0,01A | ±(5% m.v. + 5 digits) |
10,0...99,9A 1,2 | 0,1A | |
100...300A 1,2 | 1A |
2 – flexible clamp (Rogowsky coil) with diameter 400 mm – F-1
Measurement of dynamic earthing resistance (RD) with impulse wave method (4p )
Range | Resolution | Accuracy |
0,0...99,9Ω | 0,1Ω | ±(2,5% m.v. + 3 digits) |
100...199Ω | 1Ω |
choice impulse edges: 4/10ms, 10/350ms
„m.v.”- measured value