Telescopic, compact, light-weight : Length : from 354mm to 1005mm. Weight : Approx. 185g |
High-voltage detectable : The equipment, whether in stretched state is available for voltage detection in high-tension circuits (3.3kV, 6.6kV and 24kV) whether the wires involved are naked or insulated. |
Low-voltage detectable : The equipment can be used for voltage detection in low-tension circuits (80V ~ 600V) by holding the nameplate portion of the detecting head. Before-use check can easily be done by plugging in an AC 100V plug socket, without using a tester. |
Easy to recognize indication : Intermittent lighting in red of a high intensity light-emitting diode and intermittent audible sound of an electronic buzzer are readily recongnizable at a full daylight, noisy location. |
Waterproof : The detecting head, being tightly enclosed, is free from any trouble due to dust, dirt, water or the like. |
Dielectric strength : |
(a) Between Sensing tip ~ Grip portion : 50kVAC, 1 min (The detector has to be stretched). |
(b) Between Sensing tip ~ Nameplate portion : 4kV AC, 1 min. |
Construction : Waterproof (detecting head impervious to water). |
Insulation resistance : Measure the insulation resistance with the high voltage insulation tester. The areas we measure are the same as dielectric strength test. |
(a) Between Sensing tip ~ Grip portion : 1kV (The detector has to be stretched). The insulation resistance has to be more than 2000M Ohm. |
(b) Between Sensing tip ~ Nameplate portion : 1kV. The insulation resistance has to be more than 2000M Ohm. |
Leakage current test : Put high voltage on the parts listed below. |
(a) Between Sensing tip ~ Grip portion : 50kV AC, 1 min (The detector has to be stretched). The leakage current has to be 100uA or less than 100uA. |
(b) Between Sensing tip ~ Nameplate portion : 4kV AC, 1 min. The leakage current has to be 100uA or less than 100uA |
Meets EN 61010-1, EN50081-1, EN 55082-1, EN 55022, EN 61000-4-2, EN 61000-4-3 |